Description
Overview:
The ABB PE1364B Modbus TCP/DDCS Converter is a protocol converter. It is designed to facilitate communication between DDCS (Drive Control and Communication System) networks and Modbus TCP. This converter allows users to read data traffic on the DDCS interface and make it accessible on Modbus TCP networks. It is connecting directly with devices like ABB AC80, AC800, and AC4xx. PE1364B provides a robust, reliable solution for data transfer and protocol integration.
Specification | Details |
---|---|
General Information | |
Order Numbers | PE1364B (18 nodes, 8 datasets per node), PE1364B24 (24 nodes, 7 datasets per node) |
Enclosure | Metal box, mounted in a cubicle or separate enclosure |
Mounting Requirements | 4 x M5 screws, hole spacing 176 x 160 mm (W x H) |
Power Supply | |
Voltage | 24V DC (operating range 12–30V DC) |
Current Consumption | 170 mA at 24V |
Environmental Specifications | |
Enclosure Class | IP00 |
Operating Temperature | 5°C to +40°C |
Storage Temperature | -40°C to +70°C |
Physical Dimensions | |
Width x Height | 196 x 170 mm |
Depth Requirement | 50 mm |
DDCS Communication | |
Fiber Optic Type | 1.0 mm Plastic Optical Fiber (POF) or 200 µm Hard Clad Silica (HCS) fiber |
Transmission Speed | 4 Mbit |
Maximum Distance | 200 meters (200 µm HCS with TB810) or 15 meters (1.0 mm POF with TB810 or TB811) |
Modbus TCP Communication | |
Interface | RJ45 Ethernet connector |
Protocol | AnyBus S Modbus TCP |